MOD30U-30HFN1-M(GA)
MDV · HP - Split System
ENERGY STAR CertifiedAir-Source Heat Pumps →
SEER2
17.5–21BTU/Wh
HSPF2
8.4–9.1BTU/Wh
Cooling Capacity
30000BTU/hr
Refrigerant
R-410A
GWP 2088 · Higher
GWP 2088 · high impactENERGY STAR Most Efficient
MDV MOD30U-30HFN1-M(GA): SEER2 21 BTU/Wh, around the middle of the range for air-source heat pumps (category median 20 BTU/Wh).
Where this model sits
Cooling30000BTU/hr
6000median 2400060000
SEER221BTU/Wh
15.2median 2035.1
The MDV MOD30U-30HFN1-M(GA) is a 30000 BTU/hr hp - split system using R-410A, a refrigerant with high global warming potential (GWP 2088). At 21 BTU/Wh it ranks around the middle of the 12,218 certified air-source heat pumps models. Among similar-sized air-source heat pumps (within 10% of its size), it is more efficient than the peer median of 20 BTU/Wh. Comparable models from Midea in this size range average 21 BTU/Wh.
Specifications
| Efficiency | |
|---|---|
| SEER2 (best combination) | 21BTU/Wh |
| SEER2 (worst combination) | 17.5BTU/Wh |
| HSPF2 (best combination) | 9.1BTU/Wh |
| HSPF2 (worst combination) | 8.4BTU/Wh |
| EER2 (best combination) | 12.2BTU/Wh |
| COP at 5 °F | 1.92 |
| Capacity | |
| Cooling Capacity (max) | 30000BTU/hr |
| Cooling Capacity (min) | 30000BTU/hr |
| Heating at 47 °F | 30000BTU/hr |
| Heating at 17 °F | 20600BTU/hr |
| Heating at 5 °F | 20000BTU/hr |
All 25 specifications
| Configuration | |
|---|---|
| Product Type | HP - Split System |
| Compressor Staging | Continuously variable |
| Cold Climate Certified | No |
| Connected Capability | No |
| Series | MVB Series |
| Indoor-Unit Combinations Rated | 4 |
| Refrigerant | |
| Type | R-410A |
| GWP Rating | R-410A (GWP:2088) |
| Identifiers | |
| Model Number | MOD30U-30HFN1-M(GA) |
| ENERGY STAR ID | ES_1138537_MOD30U-30HFN1-M(GA)_01282023083136_4514704 |
| Partner | GD MIDEA AIR-CONDITIONING EQUIPMENT CO., LTD. |
| Date Certified | 2026-06-25 |
| Available From | 2022-10-31 |
| Markets | United States, Canada |
Documentation
We link to manufacturer documentation at its original source rather than rehosting it, so you always get the current revision.