SpecDirectory

CU-M60BAHU

Panasonic · HP - Split System

ENERGY STAR CertifiedAir-Source Heat Pumps →
SEER2

15.2–16.2BTU/Wh

HSPF2

8.2–8.6BTU/Wh

Cooling Capacity

51000–54000BTU/hr

Cold Climate

Yes

Cold climate certified
Low SEER2

Panasonic CU-M60BAHU: SEER2 16.2 BTU/Wh, lower than 80% of air-source heat pumps (category median 20 BTU/Wh).

Where this model sits

Cooling54000BTU/hr
6000median 2400060000
SEER216.2BTU/Wh
15.2median 2035.1

Lower than 80% of air-source heat pumps.

The Panasonic CU-M60BAHU is a 54000 BTU/hr hp - split system using R-454B, a refrigerant with moderate global warming potential (GWP 470). At 16.2 BTU/Wh it ranks in the bottom 20% of the 12,218 certified air-source heat pumps models. Among similar-sized air-source heat pumps (within 10% of its size), it is less efficient than the peer median of 17.1 BTU/Wh.

Specifications

Efficiency
SEER2 (best combination)16.2BTU/Wh
SEER2 (worst combination)15.2BTU/Wh
HSPF2 (best combination)8.6BTU/Wh
HSPF2 (worst combination)8.2BTU/Wh
EER2 (best combination)8.9BTU/Wh
COP at 5 °F1.80
Capacity
Cooling Capacity (max)54000BTU/hr
Cooling Capacity (min)51000BTU/hr
Heating at 47 °F54000BTU/hr
Heating at 17 °F36000BTU/hr
Heating at 5 °F39000BTU/hr
All 25 specifications
Configuration
Product TypeHP - Split System
Compressor StagingContinuously variable
Cold Climate CertifiedYes
Connected CapabilityNo
SeriesCU Series
Indoor-Unit Combinations Rated8
Refrigerant
TypeR-454B
GWP RatingR-454B (GWP:470 | Lower GWP)
Identifiers
Model NumberCU-M60BAHU
ENERGY STAR IDES_31845_CU-M60BAHU_12062024053007_20216505878
PartnerPanasonic
Date Certified2026-05-01
Available From2025-10-21
MarketsUnited States, Canada